Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report
Drinking-Water System Number: Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:
220004108 Carlisle Drinking Water System FDC01, FDC02, FDC03(R), FDC05 City of Hamilton Large Municipal Residential January 1, 2017 to December 31, 2017
Complete if your Category is Large Municipal Residential or Small Municipal Residential Does your Drinking-Water System serve more than 10,000 people? Yes [ ] No [ x ] Is your annual report available to the public at no charge on a web site on the Internet? Yes [ x ] No [ ] www.hamilton.ca/water
Complete for all other Categories
Number of Designated Facilities served: Did you provide a copy of your annual report to all Designated Facilities you serve? Yes [ ] No [ ] Number of Interested Authorities you report to:
Location where Summary Report required under O. Reg. 170/03 Schedule 22 will be available for inspection. 700 Woodward Administration Building and Compliance Support Group
Did you provide a copy of your annual report to all Interested Authorities you report to for each Designated Facility? Yes [ ]
No [ ]
List all Drinking-Water Systems (if any), which receive all of their drinking water from your system: Drinking Water System Name Drinking Water System Number None other than Carlisle System 220004108 Did you provide a copy of your annual report to all Drinking-Water System owners that are connected to you and to whom you provide all of its drinking water? Yes [ ] No [ ] Not Applicable [X] Indicate how you notified system users that your annual report is available, and is free of charge. System users are notified that the annual report is available and free of charge via the Web and Local Newspaper. Describe your Drinking-Water System. The water source of the community of Carlisle is ground water. The Carlisle water supply system consists of four wells and one elevated water storage tank servicing a population of approximately 1800 people. Carlisle Well FDC01 has a diameter of 157 mm and a depth of approximately 40 meters. Carlisle Well FDC02 has a diameter of 300 mm to a depth of 2.6 meters and a diameter of 250 mm from 2.6 meters to 36 meters. Within a treatment well house, both wells are joined to a common header for flow metering and disinfection using sodium hypochlorite (chlorine). A chlorine contact chamber is used to ensure disinfection of the water. Carlisle Well FDC03R is a 200 mm diameter, approximately 33.5 meter deep drilled ground water well under the influence of surface water (GUDI). Carlisle Well FDC05 is a 214 mm diameter and approximately 28 meter deep drilled ground water well (GUDI). Within the well house, both well discharges have separate flow metering, filtration and UV light Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 1 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report disinfection streams. The flows are combined for treatment by sodium hypochlorite (chlorine) prior to the treated water entering the distribution system. A chlorine contact chamber is used to ensure disinfection of the water. All wells are equipped with on-line chlorine residual and turbidity analyzers that continually monitor the treated water quality. Fluoridation is not carried out at the Carlisle community wells. An elevated water storage tank is located at the same site as wells FDC01 and FDC02. The storage tank has an operating capacity of 1,400 cubic meters. It was designed for peak hour water demand equalization as well as fire and emergency storage. List all water treatment chemicals used over this reporting period. Sodium hypochlorite Were any significant expenses incurred to? [ ] Install required equipment [ ] Repair required equipment [ ] Replace required equipment Please provide a brief description and a breakdown of monetary expenses incurred. Carlisle is the first community in Hamilton to have Advanced Meter Infrastructure in place for real time water use data. This project was completed in December 2017 and will assist in conservation outreach efforts. Provide details on the notices submitted in accordance with subsection 18(1) of the Safe Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to Spills Action Centre. Notification Date
Location of Adverse
AWQI
Resolution
2017-08-22
Carlisle Sampling Station A
Total Coliforms = 1 CFU/100mL
Resampled adverse location, upstream and downstream hydrants. All results passed. The adverse was not confirmed.
Microbiological testing done under Schedule 10, 11, 12 and 17, 18 of Regulation 170/03, during this reporting period. Range of Total Range of E.Coli Range of HPC Coliform Number Results Results Number of results of HPC Sample Type (min #)-(max #) (min #)-(max #) Samples (min #)-(max #) Samples CFU/100mL CFU/1mL CFU/100mL Raw – FDC01 52 0 0 NA NA Raw – FDC02 52 0 0 NA NA Raw – FDC03(R) 52 0 0 NA NA Raw – FDC05 52 0 0 NA NA Treated – FDC01 52 0 0 52 0 to 1 Treated – FDC02 52 0 0 52 0 to 6 Treated – FDC03(R) 52 0 0 52 0 to 2 Treated – FDC05 53 0 0 53 0 to 46 Distribution 211 0 0 to 1 208 0 to 12 Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 2 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the period covered by this Annual Report. NOTE: For continuous monitors use 8760 as the number of samples.
Parameter - Sample Type Turbidity – Raw – FDC01 Turbidity – Raw – FDC02 Turbidity – Treated – FDC03(R) Turbidity – Treated – FDC05 Free Chlorine – Treated – FDC01 and FDC02 Free Chlorine – Treated – FDC03(R) and FDC05 Free Chlorine – Distribution
Number of Grab Samples 52 52 8760 8760 8760 8760 365
Range of Results (min #)-(max #)
Unit of Measure
0.06 – 0.22 0.04 – 0.22 0.01 – 0.60 0.02 – 0.53 1.64 – 2.64 1.11 – 2.64 1.00 – 2.28
NTU NTU NTU NTU mg/L mg/L mg/L
Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument. Parameter Sample Date Result Value Unit of Measure N/A Summary of Schedule 23 Inorganic parameters tested during this reporting period. Parameter
Sample Date
Result Value
Unit of Measure
AWQI
mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L
0 0 0 0 0 0 0 0 0 0 0 0 0
mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L
0 0 0 0 0 0 0 0 0 0 0 0
FDC01 - Treated Antimony Arsenic Barium Boron Cadmium Chromium Fluoride Mercury Nitrate as N Nitrite as N Selenium Sodium Uranium
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-11
Antimony Arsenic Barium Boron Cadmium Chromium Fluoride Mercury Nitrate as N Nitrite as N Selenium Sodium
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13
<0.0006 <0.001 0.0910 to 0.0970 0.017 to 0.053 <0.0001 <0.001 0.06 to 0.11 <0.00005 1.23 to 2.94 <0.01 <0.002 14.8 to 23.8 0.000404
FDC02 - Treated <0.0006 <0.001 0.0890 to 0.1030 0.017 to 0.035 <0.0001 <0.001 0.06 to 0.08 <0.00005 0.53 to 3.65 <0.01 <0.002 14.6 to 38.7
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 3 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report Uranium
2017-05-11
0.000404
mg/L
0
mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L
0 0 0 0 0 0 0 0 0 0 0 0 0
mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L
0 0 0 0 0 0 0 0 0 0 0 0 0
FDC03(R) - Treated Antimony Arsenic Barium Boron Cadmium Chromium Fluoride Mercury Nitrate as N Nitrite as N Selenium Sodium Uranium
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-09
Antimony Arsenic Barium Boron Cadmium Chromium Fluoride Mercury Nitrate as N Nitrite as N Selenium Sodium Uranium
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-09
<0.0006 <0.001 0.0730 to 0.0869 0.022 to 0.027 <0.0001 <0.001 0.07 to 0.08 <0.00005 0.15 to 0.48 <0.01 <0.002 43.2 to 55.4 0.000719
FDC05 - Treated <0.0006 <0.001 0.0770 to 0.0840 0.021 to 0.028 <0.0001 <0.001 0.07 to 0.08 <0.00005 <0.01 to 0.18 <0.01 <0.002 44.4 to 58.2 0.000481
Summary of lead testing under Schedule 15.1 during this reporting period (Applicable to the following drinking water systems; large municipal residential systems, small municipal residential systems, and non-municipal year-round residential systems) Range of Range of Lead Range of pH Alkalinity Number Number of Number Results Number Results Results Location of Points of of (min #) – of Lead (min #) – (min #) – Type Points Lead Samples (max #) AWQIs (max #) (max #) Sampled Exceedances Taken mg/L pH Units mg/L Plumbing-NR 2 4 7.15 to 7.38 N/A <0.0010 to 0.0014 0 0 Plumbing-R 20 40 6.92 to 7.76 N/A <0.0010 to 0.0018 0 0 Distribution 4 4 7.08 to 7.37 311 to 319 <0.0010 to 0.0010 0 0 NR- Non-Residential R – Residential Summary of Schedule 24 Organic parameters sampled during this reporting period. Parameter
Sample Date
Result Value
Unit of Measure
AWQI
ug/L ug/L
0 0
FDC01 - Treated 1,1-Dichloroethylene 1,2-Dichlorobenzene
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
<0.2 <0.2
Page 4 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report 1,2-Dichloroethane 1,4-Dichlorobenzene Benzene Carbon Tetrachloride Chlorobenzene Dichloromethane Ethylbenzene Tetrachloroethylene Toluene Trichloroethylene Vinyl Chloride Xylene 2,3,4,6-Tetrachlorophenol 2,4,6-Trichlorophenol 2,4-Dichlorophenoxy acetic acid (2,4-D) 2,4-Dichlorophenol Alachlor Atrazine + Desethyl-atrazine metabolites Azinphos-methyl Benzo[a]pyrene Bromoxynil Carbaryl Carbofuran Chlorpyrifos Diazinon Dicamba Diclofop-methyl Dimethoate Diquat Diuron Glyphosate Malathion MCPA (2-methyl-4chlorophenoxyacetic acid) Metolachlor Metribuzin (Sencor) Paraquat Polychlorinated Biphenyls (PCB) Pentachlorophenol Phorate Picloram Prometryne Simazine Terbufos Triallate Trifluralin
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-11 2017-05-11
<0.2 <0.2 <0.2 <0.2 <0.3 <0.5 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.2 <0.25
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
2017-05-11
<0.19
ug/L
2017-05-11 2017-05-11
<0.15 <0.02
ug/L ug/L
2017-05-11
<0.01
ug/L
2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11
<0.05 <0.004 <0.33 <0.05 <0.01 <0.02 <0.02 <0.20 <0.40 <0.03 <1 <0.03 <1 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0 0 0
2017-05-11
<0.12
ug/L
0
2017-05-11 2017-05-11 2017-05-11
<0.01 <0.02 <1
ug/L ug/L ug/L
2017-05-11
<0.05
ug/L
0 0 0 0
2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11
<0.15 <0.01 <1 <0.03 <0.01 <0.01 <0.01 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0
1,1-Dichloroethylene
2017-01-16 to 2017-11-13
<0.2
ug/L
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
FDC02 - Treated
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 5 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report 1,2-Dichlorobenzene 1,2-Dichloroethane 1,4-Dichlorobenzene Benzene Carbon Tetrachloride Chlorobenzene Dichloromethane Ethylbenzene Tetrachloroethylene Toluene Trichloroethylene Vinyl Chloride Xylene 2,3,4,6-Tetrachlorophenol 2,4,6-Trichlorophenol 2,4-Dichlorophenoxy acetic acid (2,4-D) 2,4-Dichlorophenol Alachlor Atrazine + Desethyl-atrazine metabolites Azinphos-methyl Benzo[a]pyrene Bromoxynil Carbaryl Carbofuran Chlorpyrifos Diazinon Dicamba Diclofop-methyl Dimethoate Diquat Diuron Glyphosate Malathion MCPA (2-methyl-4chlorophenoxyacetic acid) Metolachlor Metribuzin (Sencor) Paraquat Polychlorinated Biphenyls (PCB) Pentachlorophenol Phorate Picloram Prometryne Simazine Terbufos Triallate Trifluralin
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-11 2017-05-11
<0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.5 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.2 <0.25
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2017-05-11
<0.19
ug/L
2017-05-11 2017-05-11
<0.15 <0.02
ug/L ug/L
2017-05-11
<0.01
ug/L
2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11
<0.05 <0.004 <0.33 <0.05 <0.01 <0.02 <0.02 <0.20 <0.40 <0.03 <1 <0.03 <1 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0 0 0
2017-05-11
<0.12
ug/L
0
2017-05-11 2017-05-11 2017-05-11
<0.01 <0.02 <1
ug/L ug/L ug/L
2017-05-11
<0.05
ug/L
0 0 0 0
2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11 2017-05-11
<0.15 <0.01 <1 <0.03 <0.01 <0.01 <0.01 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0
0 0 0 0 0 0 0 0
FDC03 (R) - Treated Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 6 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report 1,1-Dichloroethylene 1,2-Dichlorobenzene 1,2-Dichloroethane 1,4-Dichlorobenzene Benzene Carbon Tetrachloride Chlorobenzene Dichloromethane Ethylbenzene Tetrachloroethylene Toluene Trichloroethylene Vinyl Chloride Xylene 2,3,4,6-Tetrachlorophenol 2,4,6-Trichlorophenol 2,4-Dichlorophenoxy acetic acid (2,4-D) 2,4-Dichlorophenol Alachlor Atrazine + Desethyl-atrazine metabolites Azinphos-methyl Benzo[a]pyrene Bromoxynil Carbaryl Carbofuran Chlorpyrifos Diazinon Dicamba Diclofop-methyl Dimethoate Diquat Diuron Glyphosate Malathion MCPA (2-methyl-4chlorophenoxyacetic acid) Metolachlor Metribuzin (Sencor) Paraquat Polychlorinated Biphenyls (PCB) Pentachlorophenol Phorate Picloram Prometryne Simazine Terbufos Triallate Trifluralin
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-09 2017-05-09
<0.2 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.5 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.2 <0.25
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
2017-05-09
<0.19
ug/L
2017-05-09 2017-05-09
<0.15 <0.02
ug/L ug/L
2017-05-09
<0.01
ug/L
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.05 <0.004 <0.33 <0.05 <0.01 <0.02 <0.02 <0.20 <0.40 <0.03 <1 <0.03 <1 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0 0 0
2017-05-09
<0.12
ug/L
0
2017-05-09 2017-05-09 2017-05-09
<0.01 <0.02 <1
ug/L ug/L ug/L
2017-05-09
<0.05
ug/L
0 0 0 0
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.15 <0.01 <1 <0.03 <0.01 <0.01 <0.01 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 Page 7 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report FDC05 - Treated 1,1-Dichloroethylene 1,2-Dichlorobenzene 1,2-Dichloroethane 1,4-Dichlorobenzene Benzene Carbon Tetrachloride Chlorobenzene Dichloromethane Ethylbenzene Tetrachloroethylene Toluene Trichloroethylene Vinyl Chloride Xylene 2,3,4,6-Tetrachlorophenol 2,4,6-Trichlorophenol 2,4-Dichlorophenoxy acetic acid (2,4-D) 2,4-Dichlorophenol Alachlor Atrazine + Desethyl-atrazine metabolites Azinphos-methyl Benzo[a]pyrene Bromoxynil Carbaryl Carbofuran Chlorpyrifos Diazinon Dicamba Diclofop-methyl Dimethoate Diquat Diuron Glyphosate Malathion MCPA (2-methyl-4chlorophenoxyacetic acid) Metolachlor Metribuzin (Sencor) Paraquat Polychlorinated Biphenyls (PCB) Pentachlorophenol Phorate Picloram Prometryne Simazine Terbufos Triallate
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-09 2017-05-09
<0.2 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.5 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.2 <0.25
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
2017-05-09
<0.19
ug/L
2017-05-09 2017-05-09
<0.15 <0.02
ug/L ug/L
2017-05-09
<0.01
ug/L
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.05 <0.004 <0.33 <0.05 <0.01 <0.02 <0.02 <0.20 <0.40 <0.03 <1 <0.03 <1 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0 0 0
2017-05-09
<0.12
ug/L
0
2017-05-09 2017-05-09 2017-05-09
<0.01 <0.02 <1
ug/L ug/L ug/L
2017-05-09
<0.05
ug/L
0 0 0 0
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.15 <0.01 <1 <0.03 <0.01 <0.01 <0.01
ug/L ug/L ug/L ug/L ug/L ug/L ug/L
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 Page 8 of 9
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report Trifluralin
2017-05-09
<0.02
ug/L
0
Distribution Running annual average for 11.8 ug/L 0 the last four quarters. Haloacetic Acids 2017-01-16 to 2017-11-13 <5.3 ug/L 0 * The Maximum Acceptable Concentration for Trihalomethanes in the distribution is based on a running average of the results from all sampling events in the past four quarters. This running average can be found in the result value column. Total Trihalomethanes*
List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed in Schedule 2 of Ontario Drinking Water Quality Standards (O.Reg.169/03). Parameter Sample Date Result Value Unit of Measure N/A (Only if DWS category is large municipal residential, small municipal residential, large municipal non residential, non municipal year round residential, large non municipal non residential) Definitions: AWQI: Adverse Water Quality Incident CFU: Colony Forming Unit HPC: Heterotrophic Plate Count Max: Maximum mg/L: milligrams per litre Min: Minimum mL: millilitre N/A: Not Applicable
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 9 of 9