Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report Section 11, ANNUAL REPORT Drinking-Water System Number: Drinking-Water System Name: Drinking-Water System Owner: Drinking-Water System Category: Period being reported:
220004117 Freelton Drinking Water System FDF01, FDF03 City of Hamilton Large Municipal Residential January 1, 2017 to December 31, 2017
Complete if your Category is Large Municipal Residential or Small Municipal Residential
Complete for all other Categories
Number of Designated Facilities served: Does your Drinking-Water System serve more than 10,000 people? Yes [ ] No [ x ] Is your annual report available to the public at no charge on a web site on the Internet? Yes [ x ] No [ ] www.hamilton.ca/water Location where Summary Report required under O. Reg. 170/03 Schedule 22 will be available for inspection.
Did you provide a copy of your annual report to all Designated Facilities you serve? Yes [ ] No [ ] Number of Interested Authorities you report to: Did you provide a copy of your annual report to all Interested Authorities you report to for each Designated Facility? Yes [ ]
No [ ]
700 Woodward Administration BuildingCompliance Support Group
List all Drinking-Water Systems (if any), which receive all of their drinking water from your system: Drinking Water System Name None other than Freelton System
Drinking Water System Number 220004117
Did you provide a copy of your annual report to all Drinking-Water System owners that are connected to you and to whom you provide all of its drinking water? Yes [ ] No [ ] Not Applicable [X] Indicate how you notified system users that your annual report is available, and is free of charge. System users are notified that the annual report is available and free of charge via the Web and Local Newspaper. Describe your Drinking-Water System The water source for the community of Freelton is ground water. The Freelton water supply system consists of two wells and one elevated water storage tank servicing a population of approximately 780. Well FDF01 is a 250mm diameter, approximately 21 meter deep drilled ground water well. Sodium hypochlorite (chlorine) is used for disinfection prior to treated water entering the distribution system. Disinfection is achieved using a chlorine
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 1 of 6
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report contact chamber. Well FDF03 is a 300mm diameter, approximately 50 meter deep drilled ground water well. Sodium hypochlorite (chlorine) is used for disinfection prior to treated water entering the distribution system. A chlorine contact chamber is used to ensure disinfection of the water. 3
An elevated water storage tank with an operating capacity of 2840 m is available for peak hour water demand equalization as well as fire and emergency storage. Both wells are equipped with on-line chlorine residual analyzers and turbidity analyzers that continually monitor the treated water quality. Fluoridation is not carried out at the Freelton community wells. List all water treatment chemicals used over this reporting period.
Sodium hypochlorite
Were any significant expenses incurred to? [ ] Install required equipment [ ] Repair required equipment [ ] Replace required equipment Please provide a brief description and a breakdown of monetary expenses incurred There were no capital projects initiated in 2017. Provide details on the notices submitted in accordance with subsection 18(1) of the Safe Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to Spills Action Centre. Notification Date
Location of Adverse
AWQI
Resolution
We are pleased to announce that there were no Adverse Water Quality Incidents for the period of January to December 2017. Microbiological testing done under Schedule 10, 11, 12 and 17, 18 of Regulation 170/03, during this reporting period.
Sample Type Raw – FDF01 Raw – FDF03 Treated – FDF01 Treated – FDF03 Distribution N/A - Not applicable
Number of Samples
Range of E.Coli Results (min #)-(max #) CFU/100mL
Range of Total Coliform Results (min #)-(max #) CFU/100mL
Number of HPC Samples
Range of HPC Results (min #)-(max #) CFU/1mL
50 52 50 54 208
0 0 0 0 0
0 to 1 0 0 0 0
N/A N/A 50 54 208
N/A N/A 0 to 2 0 to 1 0 to 93
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 2 of 6
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report
Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the period covered by this Annual Report.
NOTE: For continuous monitors use 8760 as the number of samples.
Number of Grab Samples
Range of Results (min #)-(max #)
Unit of Measure
Turbidity – Raw - FDF01
50
0.07 – 0.40
NTU
Turbidity – Raw - FDF03
52
0.07 – 0.41
NTU
Free Chlorine – Treated FDF01
8760
0.73 – 2.15
mg/L
Free Chlorine – Treated FDF03
8760
1.38 – 2.00
mg/L
Free Chlorine - Distribution
365
1.00 – 2.03
mg/L
Parameter - Sample Type
Summary of additional testing and sampling carried out in accordance with the requirement of an approval, order or other legal instrument. Parameter Sample Date Result Value Unit of Measure N/A Summary of Schedule 23 Inorganic parameters tested during this reporting period. Parameter
Sample Date
Result Value
Unit of Measure
AWQI
mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L
0 0 0 0 0 0 0 0 0 0 0 0 0
mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L
0 0 0 0 0 0 0 0 0 0 0 0
FDF01 - Treated Antimony Arsenic Barium Boron Cadmium Chromium Fluoride Mercury Nitrate as N Nitrite as N Selenium Sodium Uranium
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-09
<0.0006 <0.001 0.0654 to 0.0700 0.021 to 0.025 <0.0001 <0.001 0.08 to 0.09 <0.00005 1.43 to 2.47 <0.01 <0.002 45.3 to 52.8 0.000292
FDF03 – Treated Antimony Arsenic Barium Boron Cadmium Chromium Fluoride Mercury Nitrate as N Nitrite as N Selenium Sodium
2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13
<0.0006 <0.001 0.0640 to 0.0720 0.017 to 0.027 <0.0001 <0.001 0.16 to 0.17 <0.00005 <0.01 to 0.05 <0.01 <0.002 24.1 to 49.7
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 3 of 6
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report Uranium
2017-05-09
0.000256
mg/L
0
Summary of lead testing under Schedule 15.1 during this reporting period (Applicable to the following drinking water systems; large municipal residential systems, small municipal residential systems, and non-municipal year-round residential systems) Range of Range of Lead Range of pH Number Alkalinity Number Number of Results Number Results of Results Location of Points of (min #) – of Lead (min #) – (min #) – Points Type Samples Lead (max #) AWQIs (max #) (max #) Sampled Taken Exceedances mg/L pH Units mg/L 0 0 Plumbing-NR 2 4 7.51 to 7.69 N/A <0.0010 0 0 Plumbing-R 21 42 6.73 to 7.86 NA <0.0010 to 0.0012 0 0 Distribution 4 4 7.11 to 7.77 291 to 296 <0.0010 to 0.0040 NR- Non-Residential R – Residential Summary of Schedule 24 Organic parameters sampled during this reporting period. Parameter
Result Value
Unit of Measure
AWQI
2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-01-16 to 2017-11-13 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.2 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.5 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.2 <0.25 <0.19 <0.15 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2017-05-09
<0.01
ug/L
0
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.05 <0.004 <0.33 <0.05 <0.01 <0.02 <0.02 <0.20 <0.40 <0.03
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0
Sample Date
FDF01- Treated 1,1-Dichloroethylene 1,2-Dichlorobenzene 1,2-Dichloroethane 1,4-Dichlorobenzene Benzene Carbon Tetrachloride Chlorobenzene Dichloromethane Ethylbenzene Tetrachloroethylene Toluene Trichloroethylene Vinyl Chloride Xylene 2,3,4,6-Tetrachlorophenol 2,4,6-Trichlorophenol 2,4-Dichlorophenoxy acetic acid (2,4-D) 2,4-Dichlorophenol Alachlor Atrazine + Desethyl-atrazine metabolites Azinphos-methyl Benzo[a]pyrene Bromoxynil Carbaryl Carbofuran Chlorpyrifos Diazinon Dicamba Diclofop-methyl Dimethoate
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 4 of 6
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report Diquat Diuron Glyphosate Malathion MCPA (2-methyl-4chlorophenoxyacetic acid) Metolachlor Metribuzin (Sencor) Paraquat Polychlorinated Biphenyls (PCB) Pentachlorophenol Phorate Picloram Prometryne Simazine Terbufos Triallate Trifluralin
2017-05-09 2017-05-09 2017-05-09 2017-05-09
<1 <0.03 <1 <0.02
ug/L ug/L ug/L ug/L
0 0 0 0
2017-05-09
<0.12
ug/L
0
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.01 <0.02 <1 <0.05 <0.15 <0.01 <1 <0.03 <0.01 <0.01 <0.01 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0
2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-01-17 to 2017-11-13 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.2 <0.2 <0.2 <0.2 <0.2 <0.2 <0.3 <0.5 <0.2 <0.2 <0.2 to 1.0 <0.2 <0.2 <0.3 <0.2 <0.25 <0.19 <0.15 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
2017-05-09
<0.01
ug/L
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.05 <0.004 <0.33 <0.05 <0.01 <0.02 <0.02 <0.20 <0.40 <0.03 <1
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
FDF03 - Treated 1,1-Dichloroethylene 1,2-Dichlorobenzene 1,2-Dichloroethane 1,4-Dichlorobenzene Benzene Carbon Tetrachloride Chlorobenzene Dichloromethane Ethylbenzene Tetrachloroethylene Toluene Trichloroethylene Vinyl Chloride Xylene 2,3,4,6-Tetrachlorophenol 2,4,6-Trichlorophenol 2,4-Dichlorophenoxy acetic acid (2,4-D) 2,4-Dichlorophenol Alachlor Atrazine + Desethyl-atrazine metabolites Azinphos-methyl Benzo[a]pyrene Bromoxynil Carbaryl Carbofuran Chlorpyrifos Diazinon Dicamba Diclofop-methyl Dimethoate Diquat
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
0 0 0 0 0 0 0 0 0 0 0
Page 5 of 6
Drinking-Water Systems Regulation O. Reg. 170/03 Section 11 Annual Report Diuron Glyphosate Malathion MCPA (2-methyl-4chlorophenoxyacetic acid) Metolachlor Metribuzin (Sencor) Paraquat Polychlorinated Biphenyls (PCB) Pentachlorophenol Phorate Picloram Prometryne Simazine Terbufos Triallate Trifluralin
2017-05-09 2017-05-09 2017-05-09
<0.03 <1 <0.02
ug/L ug/L ug/L
0 0 0
2017-05-09
<0.12
ug/L
0
2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09 2017-05-09
<0.01 <0.02 <1 <0.05 <0.15 <0.01 <1 <0.03 <0.01 <0.01 <0.01 <0.02
ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L ug/L
0 0 0 0 0 0 0 0 0 0 0 0
10.3
ug/L
0
Distribution Total Trihalomethanes*
Running annual average for the last four quarters
Haloacetic Acids 2017-01-16 to 2017-11-13 <5.3 ug/L 0 * The Maximum Acceptable Concentration for Trihalomethanes in the distribution is based on a running average of the results from all sampling events in the past four quarters. This running average can be found in the result value column. List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed in Schedule 2 of Ontario Drinking Water Quality Standards (O.Reg.169/03). Parameter Sample Date Result Value Unit of Measure N/A (Only if DWS category is large municipal residential, small municipal residential, large municipal non residential, non municipal year round residential, large non municipal non residential) Definitions: AWQI: Adverse Water Quality Incident CFU: Colony Forming Unit HPC: Heterotrophic Plate Count Max: Maximum mg/L: milligrams per litre Min: Minimum mL: millilitre N/A: Not Applicable
Annual Drinking Water Report required under Section 11, O.Reg. 170/03 Issue 4.0 (January 2018)
Page 6 of 6